MSA 2005-S, 2000 A

Popis

Closed loop

Industrial applications, current measuring of all waveforms AC, DC.

  • Chassis mount
  • Closed loop
  • High dielectric strength
  • Precise linearity
  • Precise accuracy
  • High dynamic response
  • No foucault losses in the magnetic circuit

Electrical specifications

Primary nominal RMS voltage VPN 2000 A
Primary voltage measuring range VP ± 3000 A
Output measuring resistance RM 11 Ω max @ 24 V 70 °C
Secondary nominal RMS curent ISN 400 mA
Conversion ratio KN 1:5000
Auxiliary supply voltage VC ±15 to ±24 VDC ±5 %
Current consumption IC ±22 mA + Is @ 15 VDC
Dielectric strength between:
   primary and secondary circuit VD1 6 kV – 50 Hz – 1 min

 

Overall accuracy @ IPN – TA = 25 °C XG ± 0.7 %
Overall accuracy @ IPN – TA = -40 °C…85 °C XG ± 1 %
Linearity EL < 0.1 %
Offset current @ IP = 0 – TA = 25 °C I0 ± 0.25 mA max
Thermal drift of I0 between -40 °C…+85 °C I0T ± 1 mA max
Resp.time @ 90% of IPN and di/dt 100 A / µs Tr < 100 µs
di/dt accuracy followed di/dt > 100 A / µs
Frequency bandwidth (-3 dB) f DC to 100 kHz by technology

General specifications

Operating temperature TA -40 °C…+85 °C
Storing temperature Ts -50 °C…+90 °C
Secondary coil resistance @ 70 °C Rs 25 Ω
Weight m 1550 g ± 5%

Standards

EN 50178

EN 61000-6-2

EN 61000-6-4

    + Poptávkový formulář